Product Details:
|
High-voltage electrode hot water boiler
1.Working principle
Ø The electrode is immersed in water with a certain conductivity. After power is turned on, due to the high resistance of water, current is generated, and heat is generated to turn water into high-temperature water. Water is both a heat-conducting medium and a heat-generating medium.
Ø The three-phase electrodes are arranged symmetrically in the inner cylinder to form a zero potential, and no neutral line is required.
Ø The boiler power is adjusted by raising and lowering the electrode shield.
Ø Power range: 1MW-60MW
Ø Working pressure: normal pressure/pressure
Ø Application scenarios: valley power heat storage, direct supply instead of coal-fired boilers, and flexible transformation of thermal power plants
2.Performance parameters
Type |
Normal Pressure Boiler |
Pressure Boiler |
|||||||
Model |
LDJ-4 |
LDJ-8 |
LDJ-12 |
LDJ-4 |
LDJ-8 |
LDJ-12 |
LDJ-24 |
LDJ-40 |
LDJ-60 |
Capacity(MW) |
1-4 |
5-8 |
9-12 |
1-4 |
5-8 |
9-12 |
13-24 |
25-40 |
50-60 |
Diameter(Mm) |
1100 |
1400 |
1600 |
1400 |
1400 |
1600 |
2200 |
2400 |
2600 |
Height(Mm) |
3000 |
4200 |
4800 |
3300 |
4200 |
4800 |
5200 |
7500 |
8600 |
Inlet And Outlet Size |
DN150 |
DN200 |
DN200 |
DN150 |
DN200 |
DN200 |
DN250 |
DN300/350 |
DN300/350 |
Shipping Weight(Kg) |
2000 |
2000 |
2800 |
1600 |
2200 |
3000 |
5200 |
6800 |
9200 |
Operating Weight(Kg) |
4000 |
6000 |
9200 |
4400 |
6200 |
9400 |
18200 |
22800 |
30200 |
Work Pressure(Mpa) |
Normal Pressure |
0.6 |
1.25 |
||||||
Maximum Operating Temperature(℃) |
95 |
120 |
150 |
||||||
Main Pressure Components |
Q345R/304 |
Q345R |
|||||||
Voltage |
10kV |
3.System Introduction
3.1. The high-voltage electrode hot water boiler is integrated with a high-voltage electrode boiler, a circulating water pump, a constant pressure device, a plate heat exchanger, a water treatment device and a control system.
3.2.The high-voltage electrode boiler uses water with a certain conductivity. In order to control the stability of the conductivity, a plate heat exchanger is used to isolate the primary side system and the secondary side system.